FLM-420-RLE-S Extinguishing module

Commercial Type No.: FLM-420-RLE-S
Product No.: F.01U.080.970

FLM-420-RLE-S Extinguishing module
  • Rotary switches for automatic or manual address setting
  • 2 input lines usable as independent inputs
  • LED display for status indication
  • Power supply via LSN
  • Surface or DIN rail mounting
  • Details
    Input voltage 15 V DC to 33 V DC
    Max. current consumption 7.9 mA
    Activation extinguishing system
    after initialization / during standby 3.3 kOhm
    during alarm 680 Ohm
    Max. monitoring voltage 6 V
    Max. monitoring current 1.5 mA (line short-circuit)
    Operating/display elements 2 LEDs (1 yellow, 1 red)
    Address setting 3 rotary switches for
    LSN classic mode or LSN improved version
    Automatic or manual addressing
    Connection 8 screw terminals
    Material
    Interface module PPO (Noryl)
    Surface-mount housing ABS/PC blend
    Color
    Interface module Gray white, similar to RAL 9002
    Housing Signal white, RAL 9003
    Dimensions
    with housing Approx. 126 x 126 x 71 mm(4.96 x 4.96 x 2.8 in.)
    without housing (with DIN rail adapter) Approx. 110 x 110 x 48 mm(4.33 x 4.33 x 1.89 in.)
    Weight
    with housing Approx. 390 g (13.8 ounces)
    without housing Approx. 150 g (5.3 ounces)
    Permitted operating temperature -20 °C to 50 °C (-4 °F to 122 °F)
    Permitted storage temperature -25 °C to 85 °C(-13 °F to 176 °F)
    Permitted relative humidity < 96%
    Classes of equipment as per IEC 60950 Class III equipment
    Protection class as per IEC 60529 IP 54

    Images

     

    Features

    LSN vds
     
  • Certificates (2)
    Title Type Language
    Declaration of Conformity PDF
    VdS PDF
     
  • Documents (5)