GE3‑12WR 12 V Strobe and Horn Strobe

GE3‑12WR 12 V Strobe and Horn Strobe
  • Silence the horn while strobes flash
  • Use the SuperSlide™ feature for easy testing
  • Wide voltage range; 8 VDC to 17.5 VDC
  • Four candela choices: 15, 30, 60, or 75 cd
  • Select high or low frequency, high or low volume, and temporal Code 3 or continuous tone pattern
  • Rugged die‑cast metal mounting plate
  • Details
    Input voltage 12 VDC or FWR nominal
    Voltage range 8 to 17.5 VDC or FWR
    Strobe current ratings:
    15 cd 163 mA RMS
    30 cd 212 mA RMS
    60 cd 331 mA RMS
    75 cd 436 mA RMS
    Relative Humidity Up to 93% non‑condensing
    Temperature (Operating) +32°F to +120°F (0°C to +49°C)
    Dimensions (H x W x D) 5.0 in. x 4.5 in. x 2.5 in. (12.7 cm x 11.4 cm x 6.4 cm)
    Horn (Continuous, 2400 Hz)
    Audible Device Current (maximum) 29 mA RMS
    Sound Output (maximum range) at 10 ft (3 m) 79 dBA to 84 dBA
    Horn (Continuous, Mechanical)
    Audible Device Current (maximum) 26 mA RMS
    Sound Output (maximum range) at 10 ft (3 m) 79 dBA to 83 dBA
    Horn (Temporal Code 3, 2400 Hz)
    Audible Device Current (maximum) 29 mA RMS
    Sound Output (maximum range) at 10 ft (3 m) 76 dBA to 81 dBA
    Horn (Temporal Code 3, Mechanical)
    Audible Device Current (maximum) 26 mA RMS
    Sound Output (maximum range) at 10 ft (3 m) 75 dBA to 80 dBA
    Chime (Continuous)
    Audible Device Current (maximum) 13 mA RMS
    Sound Output (maximum range) at 10 ft (3 m) 64 dBA* to 65 dBA*
    * If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application.
    Chime (Temporal Code 3)
    Audible Device Current (maximum) 13 mA RMS
    Sound Output (maximum range) at 10 ft (3 m) 63 dBA* to 64 dBA*
    * If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application.
    Whoop
    Audible Device Current (maximum) 55 mA RMS
    Sound Output (maximum range) at 10 ft (3 m) 77 dBA to 83 dBA

    Images

     
  • Certificates (4)
    Title Type Language
    UL PDF
    UL PDF
    FM PDF
    CSFM PDF
     
  • Documents (2)
     
 

Product variants

GEC3‑12WR 12 VDC Horn Strobe Unit

These red, 12 VDC horn/strobes have field‑selectable strobe intensities of 15 cd, 30 cd, 60 cd, or 75 cd, and horns with high or low frequency, high or low volume, and temporal (Code 3) or continuous tone pattern.

Commercial Type No.: GEC3-12WR
Product No.: 4.998.140.286

 
GES3‑12WR 12 VDC Strobe Unit

These red, 12 VDC strobe units have field‑selectable intensities of 15 cd, 30 cd, 60 cd, or 75 cd.

Commercial Type No.: GES3-12WR
Product No.: 4.998.140.282

 
 

Accessories

AVS-44 24VDC TO 33VDC RED

Commercial Type No.: AVS-44
Product No.: F.01U.003.662

 

AVS44-W GANG SYNC MOD 24-33V WHT

Commercial Type No.: AVS44-W
Product No.: F.01U.003.697

 
 
AVSM-R Synchronization module, Gentex, red

AVSM-R Synchronization module, Gentex, red

Synchronization module for use with all Gentex synchronizable notification appliances except the HS24 Series and the ST24 Series.

Not Available.

Commercial Type No.: AVSM-R
Product No.: F.01U.003.704

 
AVSM-W Synchronization module, Gentex, white

AVSM-W Synchronization module, Gentex, white

Synchronization module for use with all Gentex synchronizable notification appliances except the HS24 Series and the ST24 Series.

Not Available.

Commercial Type No.: AVSM-W
Product No.: F.01U.003.703

 
 
GSB Surface backbox, 5.6x4.6x1.5

GSB Surface backbox, 5.6x4.6x1.5", red

5.6 in. x 4.6 in. x 1.5 in. (14.1 cm x 11.6 cm x 3.7 cm)

Commercial Type No.: GSB
Product No.: F.01U.020.756