GEC24‑15/75WR 15/75 cd Horn Strobe (red)

Commercial Type No.: GEC24-15/75WR
Product No.: 4.998.137.913

GEC24‑15/75WR 15/75 cd Horn Strobe (red)
  • Silence the horn while strobes flash
  • Evacuation tone
  • Use the SuperSlide feature for easy testing
  • Wide voltage range; 16 to 33 VDC or FWR
  • Select high or low frequency, high or low volume, and temporal Code 3 or continuous tone pattern
  • Rugged die‑cast metal mounting plate
  • Details
    Input voltage 24 VDC or VFWR nominal
    Voltage range 16 to 33 VDC or FWR
    Strobe Current (maximum) 96 mA RMS; 135 mA FWR
    Relative Humidity Up to 93% non‑condensing
    Temperature (Operating) +32°F to +120°F (0°C to +49°C)
    Horn (Continuous, 2400 Hz)
    Audible Device Current (maximum) 28 mA RMS; 48 mA FWR
    Sound output (maximum range) at 10 ft (3 m) High output: 86 dBA; Low output: 78 dBA
    Horn (Continuous, Mechanical)
    Audible Device Current (maximum) 25 mA RMS; 44 mA FWR
    Sound output (maximum range) at 10 ft (3 m) High output: 84 dBA; Low output: 76 dBA
    Horn (Temporal Code 3, 2400 Hz)
    Audible Device Current (maximum) 28 mA RMS; 48 mA FWR
    Sound output (maximum range) at 10 ft (3 m) High output: 83 dBA; Low output: 75 dBA
    Horn (Temporal Code 3, Mechanical)
    Audible Device Current (maximum) 25 mA RMS; 44 mA FWR
    Sound output (maximum range) at 10 ft (3 m) High output: 81 dBA; Low output: 73 dBA*
    * If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application.
    Chime (Continuous)
    Audible Device Current (maximum) 15 mA RMS; 30 mA FWR
    Sound output (maximum range) at 10 ft (3 m) High output: 71 dBA*; Low output: 68 dBA*
    * If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application.
    Chime (Temporal Code 3)
    Audible Device Current (maximum) 15 mA RMS; 30 mA FWR
    Sound output (maximum range) at 10 ft (3 m) High output: 71 dBA*; Low output: 68 dBA*
    * If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application.
    Whoop
    Audible Device Current (maximum) 56 mA RMS; 62 mA FWR
    Sound output (maximum range) at 10 ft (3 m) High output: 83 dBA; Low output: 72 dBA*
    * If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application.

    Images

     
  • Certificates (2)
    Title Type Language
    FM PDF
    CSFM PDF
     
  • Documents (2)
     
 

Accessories

AVS-44 24VDC TO 33VDC RED

Commercial Type No.: AVS-44
Product No.: F.01U.003.662

 
AVSM-R Synchronization module, Gentex, red

AVSM-R Synchronization module, Gentex, red

Synchronization module for use with all Gentex synchronizable notification appliances except the HS24 Series and the ST24 Series.

Not Available.

Commercial Type No.: AVSM-R
Product No.: F.01U.003.704

 
 
GSB Surface backbox, 5.6x4.6x1.5

GSB Surface backbox, 5.6x4.6x1.5", red

5.6 in. x 4.6 in. x 1.5 in. (14.1 cm x 11.6 cm x 3.7 cm)

Commercial Type No.: GSB
Product No.: F.01U.020.756